Nfpa 13 draft curtain.
888 917 8777 us smoke and fire corporate video from u s.
Draft curtains are also required by nfpa 13 in buildings where an early suppression fast response esfr is adjacent to standard response systems.
Nfpa 13 requires closely spaced sprinklers with a draft curtain around unenclosed moving stairways staircases or similar unenclosed floor openings which are not large 20 feet or more across and 1000 sqft or greater as an alternative to the enclosure of the vertical opening nfpa 13 8 15 4 1 in 2016 and 9 3 5 1 in 2019.
According to nfpa 13 draft curtains need to be 2 feet deep but the ibc code commentary refers to 18.
Paragraph 3 3 8 draft curtain of nfpa 13 2016 standard for the installation of sprinkler systems defines draft curtains as a continuous material protruding downward from the ceiling to create a reservoir for collecting smoke and heat.
Icc ac 77 listed for elevator door smoke containment to remove the need to pressurize the hoistway or have lobby doors on hold open.
Smoke fire on vimeo.
It references nfpa 204 2015 standard for smoke and heat venting for additional information.
Curtains also rate glass up to two hours and are used in lieu of static glass draft curtains per nfpa 13.
With standard response sprinklers a draft curtain of noncombustible construction and at least 2 ft 600 mm in depth shall be required to separate the two areas.